Multi-line 2 ALC Application Software series 4x

Multi-line 2 ALC Application Software series 4x

You have chosen to download our software.

Within a few seconds, you will receive an email containing a download link.

Having trouble using the software? Please contact support@deif.com. 

Best regards, 

DEIF A/S

The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software

4.13.0

PM compatibility version 1.23.1.

New features:

  • Load-groups are now able to close on a dead busbar in AUTO mode. This can be activated via Modbus commands, Modbus control register or M-Logic.
  • Eight low frequency alarms are added. These are placed in menus 1000-1070.

Changes:

  • Faster execution of load-groups closing.
  • Four output relays on terminals 118-119, 118-120, 121-122 and 123-124 are now configurable.

4.13.0

15. 06. 2021

PM compatibility version 1.23.1.

New features:

  • Load-groups are now able to close on a dead busbar in AUTO mode. This can be activated via Modbus commands, Modbus control register or M-Logic.
  • Eight low frequency alarms are added. These are placed in menus 1000-1070.

Changes:

  • Faster execution of load-groups closing.
  • Four output relays on terminals 118-119, 118-120, 121-122 and 123-124 are now configurable.

4.12.0

26. 11. 2020

PM compatibility version 1.21.0.

New features:

  •    Configurable amount of units for triggering Fatal CAN Error alarm is added in menu 8800.

Changes:

  •    Support of ASC-4 redundancy.

Corrections:

  •    Corrected that selection of ‘Number of PMS units’ and ‘PMS CAN baud rate’ previously would only work with default settings. and an issue with redundancy.

4.11.0

13. 02. 2020

PM compatibility version 1.16.0
Includes version 1.15.0

New features:

  •    Now possible to open and close LG's while position failure is present.
  •    Block LG fail classes added
          • Position failure alarms set default to LG Block fail class.

Corrections:

  •    Corrected ALC Breaker Feedback Emulation.

4.10.1

10. 01. 2020

PM compatibility version 1.16.0

Corrections:

  •    Horn relay now working
  •    M-Logic PMS flags for GB/MB closed now working 
  •    LG(load group) pos. fail alarm now possible when LG is disabled

4.10.0

12. 12. 2019

PM compatibility version 1.16.0

Features:

  •    32 DG/Mains support
          • Support of 32 DG's in ID range 1-32 (AGC-4/200, version 4.65.0 required).
          • Support of 32 Mains in ID range 1-32 (AGC-4/200, version 4.65.0 required).
          • Support of 16 ASC's in ID range 25-40 (ASC-4, version 4.06.0 required).
          • Support of  8 ALC's in ID range 25-40.
  •    Support of ASC PV and Battery.
  •    Heavy Consumer logic added.
  •    Flip/Flops added to M-logic.

Changes:

  •    Disconnect Load can now be set to 200 % and 999 sec.

Corrections:

  •    Corrected: Tripped open relay hanging on redundant unit.
  •    Corrected: LG's are not opened in AUTO mode when disabled.
  •    Corrected: Digital input alarms are not activated by input.

4.00.1

29. 01. 2018

Corrections:

  • In some instances, all fail classes were initialised to "Shutdown" unintentionally.

4.00.0

30. 10. 2017

PM compatibility version 1.15.0
  
Features:
1- Includable in Power Management application type "Standard" together with AGC-4 and AGC 200.
a) Up to 16 gensets.
  b) Up to 16 mains.
c) Up to 8 BTBs/ALCs in plants.
d) Spinning reserve support.
2- Able to close and open breakers according to available power from DG. 
3- Able to place the ALC in mains load point.  

DEIF 제품을 완전하게 활용하기 위해서는 DEIF에서 제공하는 업데이트를 설치하도록 항상 권장하고 있습니다.

업데이트된 소프트웨어는 언제나 무료로 www.deif.com의 “소프트웨어”에서 “소프트웨어 내려받기”를 통해 내려받기할 수 있습니다.

질문 또는 제품 관련 소프트웨어에 관한 문의는 DEIF A/S +45 96149614 또는 해당 지역의 DEIF 사무소로 연락해 주시기 바랍니다. 그 외에도, support@deif.com로 이메일을 보내 주시면 언제든지 도와드릴 준비가 되어 있습니다.