Multi-line 300 PPU 300 ver. 1.x.x.

이 소프트웨어는 다음 DEIF 제품에 적용됩니다.

다운로드 예정입니다 1.0.7.0

마지막 버전 이후 변경된 주요 변경 사항은 다음과 같습니다.

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.11.0

PPU 300:

New features:

  • Support for the new IOM3.2 and IOM3.3 cards.
  • Derate of nominal power is now possible with an analogue input.

Correction:

  • Fixed an issue where PICUS supervision would update if the regulator type was changed.
  • Fixed an issue where EIM3.1 relay 4 wire breaker supervision was not working.
  • Fixed an issue where IOM3.4 custom texts could be mixed up if more than one card were used. This fix result in a break of backward compatibility, if custom text has been used on IOM3.4 cards.
  • Fixed an issue where adding a previously used extension rack to a new system could cause the controller to restart.
  • Fixed an issue where connection to an extension unit could cause the controller to restart in a system with more than two extension units.

DU 300:

New features:

  • Support of IOM3.2 and IOM3.3.

버전 날짜 설명

1.0.7.0

09-06-2020

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.11.0

PPU 300:

New features:

  • Support for the new IOM3.2 and IOM3.3 cards.
  • Derate of nominal power is now possible with an analogue input.

Correction:

  • Fixed an issue where PICUS supervision would update if the regulator type was changed.
  • Fixed an issue where EIM3.1 relay 4 wire breaker supervision was not working.
  • Fixed an issue where IOM3.4 custom texts could be mixed up if more than one card were used. This fix result in a break of backward compatibility, if custom text has been used on IOM3.4 cards.
  • Fixed an issue where adding a previously used extension rack to a new system could cause the controller to restart.
  • Fixed an issue where connection to an extension unit could cause the controller to restart in a system with more than two extension units.

DU 300:

New features:

  • Support of IOM3.2 and IOM3.3.

1.0.5.0

17-12-2019

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.11.0

PPU 300

New features:

  • Fixed that the display couldn't show negative values on graphs.
  • Live data screens can now be configured by the user.
  • Enhanced Backup/Restore: Restoring of CODESYS is now optional.
  • Fixed that the alarm "Different single-line diagram" would trigger during broadcast of a single-line.
  • Continous breaker: Configuration requiring only one output is now possible.
  • "Fast overcurrent" now has configurable max. range.
  • Breaker feedback: Configuration requiring only one input for feedback is now possible.
  • Support for Network Time Protocol (NTP).
  • Command sources: Setting of permissions for each individual Local/Remote source (PICUS, Display, Modbus, I/O or CustomLogic) is now possible.
  • Alarms can now be tested individually.
  • Support for ACM3.2 card.
  • Modbus: Registers for alarm trip value is now available.
  • Alarm "Inverse time overcurrent": Threshold is now configurable.
  • Redundant breaker feedback is now possible.
  • Spring loaded breaker: Arming of spring is now possible via input.
  • Breaker tripping and opening can now be assigned to individual outputs.
  • AVR can now be tripped by specific alarm actions.
  • Single line: Support for 32 controllers.
  • Flexible Modbus: User configuration of register mapping and support for additional servers.
  • Alarm details now include number of times the alarm was triggered.
  • Nominal settings: 4 sets are now available.
  • User interfaces: Different languages are now supported.
  • Modbus: Registers for Date/Time are now available.
  • Configurable alive/watchdog functionallity is now available.
  • IO Extension units: This feature allows expansion of a ML 300 system with additional decentralized racks containing the desired I/O cards.
  • Firmware update: Replacement cards can be updated without using the utility software
  • Firmware upgrade: In case of controller not beeing ready for update, detailed information about cause is now shown.
  • CODESYS: Improved I/O response time.

Changes:

  • Fixed that name of parameter group "Power supply" in relation to "EIM" was misleading. Moved to the "Hardware" section.
  • Fixed that naming of GAM3.2 I/O's did not comply with naming of other I/O's.
  • Fixed that GOV and AVR parameters did not use the same layout.
  • Minimum OK frequency minimum value and Minimum OK voltage changed to 70 %.
  • Not possible to set inhibits on "System not OK" alarm.

Corrections:

  • Fixed that software version check was only made on the first card in a rack.
  • Fixed that configurable I/O's could maintain their state after beeing unconfigured.
  • Fixed that alarm actions not allowed for a given controller type could be selected anyway.
  • Fixed that event "Start enabled deactivated" could register, even if conditions were not met.
  • Fixed that alarms for "Power import" were missing on BTB.
  • Fixed that changing the calculation method for "Q nominal" would not reflect on the HMI custom view.
  • Fixed general error in sync check.
  • Fixed that some labels in the PICUS menu hierarchy would be truncated.
  • Fixed that BTB blackout close would display the wrong pop-up text ("Busbar A voltage/frequency not OK").
  • Fixed that removing input function from an Analogue output did not reset the Analogue output to "0".
  • Fixed that Active/Reactive power differential counter pulse functionallity did not activate when importing power, only when exporting.
  • Fixed that "Running hour counters" were missing in CustomLogic.
  • Fixed that inhibit "ACM wirebreak" did not reflect the correct state.
  • Fixed that in an engine stop sequence during "Crank off time", if a "Stop command" was issued and the engine had already stopped, the "Crank off timer" was not aborted.
  • Fixed that alarms for P and Q load sharing failure were active during load share ramp-up.
  • Fixed that regulation delay for GOV and AVR was ignored during engine start.
  • Fixed that GOV and AVR regulation would continue during engine stop sequence.
  • Fixed that "Power derate" would wrongly also affect "Breaker open point".
  • Fixed that the alarm "Close failure" on a "Compact breaker" would trigger prematurely.
  • Fixed that some engine states were not available in CustomLogic.
  • Fixed that regulation delay for GOV and AVR was ignored during engine start.
  • Fixed that alarms for "Phase sequence error" were reversed with regards to A/B side.
  • Fixed that requesting "Reset to offset" on GOV or AVR regulator would result in output values not matching the setting in parameters "GOV/AVR output offset".
  • Fixed that the triggered value in alarm details would not be updated if an alarm was re-triggered.
  • Fixed non-responsive Modbus commands related to breaker operations.
  • Fixed the default parameter values for Ti, GOV and AVR manual regulator.
  • Fixed that AVR regulator mode "Fixed Voltage" did not "freeze" the regulator output, when the system lost one or more of the AC measurements.
  • Fixed that alarms with fail class "Block" would not abort the synchronize sequence.
  • Fixed that "SI-unit" label was repeated on some parameters settings.
  • Fixed that digital inputs were unavailable in CustomLogic.
  • Fixed that on the Supervision screen in PICUS the actual state of the busbar and the color representing it would mismatch.
  • Fixed that the alarm "Redundancy broken" had wrong trigger conditions.
  • Fixed that the alarm "Protection set point out of range" had wrong trigger conditions.
  • Fixed that "GAM3.2 status OK" was available as I/O source in PICUS, even when GAM3.2 was not part of the controller configuration.
  • Fixed that the pop-up message "Breaker close cancelled" did not show when conditions were in fact met.
  • Fixed that "Power derate curve" was limited to a max. setting of 200. Increased to 1000.
  • Fixed that "Derate" functionallity did not use the same base for "Power Available" calculation in [%] and in [kW], thus resulting in conflicting values.
  • Fixed that if a blackout is detected (real or loss of measurements) during the synchronisation part of a close sequence the sequence would be cancelled.
  • Fixed that supervision of SCs in PICUS would show shore measurements where ship measurements were supposed to be shown.
  • Fixed that the Backup and Restore action buttons after a restore were no longer shown in the PICUS menu.
  • Fixed that the alarm "Inverse time over-current" were not available for use on "Outputs".
  • Fixed that alarm "Busbar Phase sequence error" was unavailable in CustomLogic and Outputs.
  • Fixed that certain Modbus addresses could not be used as commands.
  • Fixed that "Operations counter" did not work for external breakers.
  • Fixed that "Acknowledge alarms" in combination with the "Alarm TEST" functionallity could result in a controller restart.
  • Fixed that CustomLogic ICC flags could become unavailable.
  • Fixed that alarms related to Generator protections would remain triggered if "Delay" was set to 0.0 seconds.
  • Fixed false detection of "Engine running" due to "noisy" busbar.
  • CODESYS: Fixed that some features in libraries and on Modbus, related to alarms, were missing.
  • Fixed that "Engine ready delay" would be ignored on SGs.
  • Fixed that on the display the "Counters" screen would show irrelevant entries.
  • Fixed that alarm and status for "Voltage or frequency not OK" did not trigger/update according to the settings.
  • Fixed that status for "Voltage and frequency OK" did not respect the parameter "Delay" settings.
  • Fixed that status text "Regulator frozen" could be shown when engine was in "stopped" state.
  • Fixed that Regulator ramp up/down did not work when operating in load share mode.
  • Fixed that alarm "Earth inverse time over-current" did not trip according to the settings.
  • Fixed that the alarm "CODESYS configuration conflict" would trigger repeatedly when downloading the CODESYS application.
  • Fixed inconsistent operation of the Regulator ramp functionality.
  • Fixed that CustomLogic could stop working if the controller was power cycled immediately after "write" of a new CustomLogic configuration.
  • Fixed falsely detection of Volt/Hz due to missing data from the ACM card.
  • Fixed that inhibit functionallity was not available for NEL groups.
  • Fixed that the Regulator status screen could show wrong values.
  • Fixed that error in CustomLogic menu configuration could result in a system error (Debug.lock).
  • Fixed a potential issue with inhibits not beeing updated.
  • Fixed that "Engine start-and-close" in combination with "Blackout close" would close the breaker before the engine was running.
  • Fixed that, in "I/O Configuration", inputs of type "DI" would show as "Undefined" when used for CustomLogic.
  • Fixed that "Derate" functionallity did not influence "Power Available" calculation correctly, thus affecting load share.
  • Fixed "Status OK" handling on ACM3.2.

DU 300

New features:

  • Extended alarm information.
  • Support of ACM3.2 V.1.0.0.0.
  • Support of Trip breaker outputs.
  • Support of /IO extension unit.

Changes:

  • Version page layout.
  • Backup and restore information.

Corrections:

  • Text bug in live views.
  • DU shows random info message.
  • Display showing wrong version number.
  • ApplState not updating text.
  • Backup from the display shows undefined text in information window.
  • Missing text for View design.
  • Restore info page: Not all cards is shown.
  • Display does not update alarm and event texts, when the custom text is changed on external breaker.
  • Backup status should handle error status.
  • Possible to enter alarm sub-menus with an empty alarms list.
  • Parameter settings are shown on the display, when setting up digital outputs.

1.0.4.1

04-03-2019

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.10.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

New features:

  • Support for multiple menu levels.
  • Display shows a pop-up window for the user before going into service mode.
  • Informs the user about development of the software.

Changes:

  • Support for PlantSupervision ver 1.0.5.0.

Corrections:

  • IOM3.4: DO's are not shown on display and in PICUS.
  • Display is not loading min. and max. from parameters when they are changed.
  • Power derate temperature is not shown on DU until power cycle.
  • When changing type, DU sometimes freezes until it restarts.
  • DU300 reboot in view designer.
  • Not able to close alarm pop-up.
  • Alarm "trigger value" is not updated if the alarm is already in the alarm list.
  • DU300 does not check versions for individual REST resources.
  • View designer cannot add counters to counters template.
 

1.0.4.1

19-11-2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

  • No changes

 

 

1.0.4.0

06-07-2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300

New features:

  • Now possible to use 16 controllers in single line

DU 300

  • No changes

 

1.0.3.0

20-04-2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300 

New features:

  • CODESYS add-on
  • Frequency-dependent droop regulation
  • Support of GAM3.2 module with stand-alone possible
  • Able to abort "Lamp test" dialogue box
  • Power ramp configuration improved for better user experience
  • Selectable offsets for fixed P, Q and CosPhi regulation
  • Alarms made available in custom logic
  • Analogue I/O made available in custom logic
  • Parameter values made available in custom logic
  • Use external analogue signal as regulator set point
  • Alarm for F/V not OK made independent of GOV/AVR configuration
  • Power regulator set point range extended to -100 % to +100 %
  • GOV/AVR status display on PICUS and display
  • Regulation on SG 
  • Freeze regulation
  • Support of IOM3.4
  • Analogue value compare and operate function in custom logic

Changes: 

  • Optimised menu layout for better user experience
  • Improved ACM firmware update sequence

Corrections:

  • Compact breaker, optimised spring load sequence
  • "Blackout detection mismatch" functionality corrected
  • Fixed missing trip alarms
  • Manual regulation not possible with certain regulator settings
  • Fixed that "GB open-and-stop command" was ignored
  • Fixed that running detection by means of digital input could be delayed (affecting "Engine ready LED")
  • Fixed that in manual regulation mode, relay output could sometimes be left in "activated" state
  • Fixed that "Remove start" input could cause unintended short activation of crank relay
  • Fixed that cancelling a stop sequence could result in engine stopping anyway
  • Fixed that command "Open generator breaker and stop engine" could leave engine running
  • Fixed that running detection would not terminate crank timer
  • Fixed that alarms "GOV and AVR regulation error" would not be triggered
  • Alarms are always shown, even if configured as "suppressed"
  • Active start block alarm can no longer abort cooldown sequence
  • Genset temperature power derate functionality improved
  • "Start engine and close GB" command is now blocked by "Block engine start" command
  • Alarm on controller with breaker feedback error could result in breaker opening and engine stopping
  • DG suddenly becoming last controller on busbar during de-load, would trip its breaker
  • Detection of "Vector mismatch" improved
  • Fixed that "Freeze regulation" could leave relay output in "activated" state
  • Fixed that "BTB trip" command did not cancel synchronisation
  • Engine state in switchboard will now resolve to "Ready" instead of "Not Ready"

DU 300

New features:

  • Livedata configurator (View design)
  • Regulator screen (GOV/AVR)
  • Livedata dynamic reload integration
  • Message box popup

Changes:

  • Added display specific support for introspecting memory data
  • Update ID and labels on pair screen when entering the screen
  • Custom curves max precision changed from 2 to 8
  • Support for REST 1.0.4.0
  • Improvement to log output
  • Added direction to command list

Corrections:

  • DU relay not working
  • ML300 Backwards compatibility issues of DU
  • Parameter graph, special case fail
  • Livedata scales are not appearing
  • Event log was not telling which "command" (button) was pressed.
  • Blocking pop-up on DU 300 if controller software does not match.
  • Counter pop-ups now working correctly.
  • Display alarm list deadlock removed.
  • DU 300 able to change from service mode to app mode.
  • Inhibit counter on the parameters was showing wrong number of inhibits
  • Comma insted of dot between the (rack#,slot#) presentation of card name
  • Identify did not work when logged on
  • Corrections to dynamic reload of livedata
  • Corrections to eventlog navigation
  • Update value list on changes
  • Applying broadcast storm filter on startup
  • Display not showing Priority
  • Pair controller not working correctly with rework.

 

1.0.2.0

29-09-2017

New features:

  • Acces to all alarm status information from CODESYS
  • Extended status information for alarm functionblocks in CODESYS   

Changes: 

  • Software mismatch on hardware module(s) alarm only occur if first, second or third digit on IO card version is changed
  • New EIM 3.1 software 2.0.1.0

1.0.1.0

25-08-2017

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.6.0

PPU 300 

New features:
   1  - 4 directional over-current alarms have been added to BTB (ANSI 67).
   2  - 2 directional over-current alarms have been added to SC and SG (ANSI 67).
   3  - Support of lamp test function.
   4  - Support of controller identify function.
   5  - Active regulator mode will be deactivated if a new is requested.
   6  - Additional information regarding alarms, breaker-, busbar- and generator status made available on Modbus.
   7  - Added "Critical process error"" alarm.
   8  - Last DG will trip if no other feeders are closed in the plant.

Changes:
   1  - "Power supply" parameter menu renamed to "Hardware".
   2  - "Network" parameter group moved to "Hardware" instead of "Utility". 
   3  - "Reset ratio" renamed to "Hysteresis" for protection alarms.
   4  - General check that "Nominal settings" cannot be configured to 0.
   5  - "Fixed power factor" renamed to "Fixed CosPhi".
   6  - "Analog" renamed to "Analogue".
   7  - "System not OK" alarm action is changed to "Warning".
   8  - New ACM 3.1 software 4.0.1.4.
   9  - New PCM 3.1 software 2.0.0.2.
   10 - The others are version 1.0.3.0.
   11 - "Directional over-current" alarm min. and max. set points have been extended to -300 % and 300 %.
   12 - Only one regulator request is accepted if more have been received.
   13 - It is possible to configure action on "System not OK" alarm.

Corrections:
   1 - Controller types SC, SG and BTB stop synchronising if measure feedback disappears.
   2 – Regulator could freeze if regulators were used in custom logic.
   3 - Regulator continued to regulate after feedback failure on GB.


DU 300

New features:
- Implemented first part of custom stylesheets
- Curves have been added to parameters
- Lamp test
- Identify feature to communication screen
- Units change on display
                      
Changes:
- Navigation and editing in I/O input text is now possible from the keyboard
- Default live data views updated
- Edit line design has been updated
- Updated counter screen to use states
- Default text in keyboard will show resolution
- Live data screens dynamic update (step 1)
- REST version control improvement step 1 (A+B match)
- REST version control improvement step 2 (new REST resource implementation)
- Live data dial meter and vertical bar widgets improved
- Production screen changed to versions screen, production data now visible in about screen
- Added DNS possibility to communication screen
- Added IPv6 address to communication screen
- Live data using REST to build screen and widgets
- Terminal values updated to only show allowed precision
- Updated help screens
                      
Corrections:
- Custom inhibit does no longer clear other inhibit flags
- Placeholder text from previous screen does no longer influence logon screen
- Handling of empty list in pair screen
- Pair screen automatically keeps rescanning for controllers if previously connected to a controller
- Elements in parameters are represented in the same order as in the base unit
- Preparation of lists in the application improved
- Removed dot key from keyboard when value is integer, or precision is zero
- Network off pop-up did not show the first time the display lost connection
- Do not allow user to press OK in empty pair list
- Cardlist serial to be a string instead of integer
- Display reboots after setting up AVR
- No longer showing all functions when function groups is empty
- Cleaned up warnings
- Not able to enable/disable the alarm "Ethernet redundancy broken"
 

1.0.0.3

12-04-2017

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.5.0

 

PPU 300

Corrections:
   1- Trip and stop action did not stop the engine in switchboard mode 
   2- Customlogic inputs was evaluated wrong in scan
   3- Sync. type was changed back from Static to dynamic after a power cycle

 

DU 300

No changes

1.0.0.2

14-03-2017

Corrections:

  • Start and close command now works correctly if “Voltage and frequency OK” timer has been increased.
  • Open and stop command can also stop the engine if breaker is opened, when command has been sent.

 


1.0.0.0

21-12-2016

PPU 300: Initial release

DU 300 ver. 1.0.5.0:

New features:

  • Added placeholder text when the label is completly empty, when you enter an I/O name, the current name of the IO will be shown.
  • Support of 4 line pop-up in the display.
  • Displays the variant on the info/about screen.
  • New pair feature (select base unit).

Changes:

  • DU registration of 4 new languages.
  • DU REST 1.0.2.0 support.
  • Update DU help files.
  • Added REST version to "About screen" in row 3.
  • Made it possible to take pictures of the first pair screen

Corrections:

  • Changed home screen Alarm 8000002 to Alarms 800025 to match the path.
  • Removed two arrows that were shown in parameter groups that was not supposed to be there.
  • Display could have problems, connecting to base units if it was connected in a daisy chain.
  • Making the algorithm responsible for showing/hiding pop-up windows.
  • Updating status text, and diodes in DU is made faster.
  • Crash in start-up sequence removed.
  • Corrected some filtering of allowed functions.
  • Remove illegal references to parameters.
  • Incorrect text shown when valueList had less than 2 elements removed.
  • If alarm screen is detected in the screen history, the current screen is rewound to that alarm screen.
  • DU updating speed improved.
  • Pop-up header characters clip adjusted.
  • IO scale: impossible to select a custom scale with only 1 point.
  • Header text initialised.
  • Pairing pop-up cuts of text on very long labels.
  • Controller for selecting base unit.
  • Appending empty unit to analogue output functions not possible.
  • DU start-up screen has been corrected.
  • Label corrected to "Restart" display instead of "Reset".

DEIF 제품을 완전하게 활용하기 위해서는 DEIF에서 제공하는 업데이트를 설치하도록 항상 권장하고 있습니다.

업데이트된 소프트웨어는 언제나 무료로 www.deif.com의 “소프트웨어”에서 “소프트웨어 내려받기”를 통해 내려받기할 수 있습니다.

질문 또는 제품 관련 소프트웨어에 관한 문의는 DEIF A/S +45 96149614 또는 해당 지역의 DEIF 사무소로 연락해 주시기 바랍니다. 그 외에도, support@deif.com로 이메일을 보내 주시면 언제든지 도와드릴 준비가 되어 있습니다.