New features

  • Three pump logic routines can now be set up to control the pumping of a substance.
  • Implement ECU diagnostic to enable run coil and ECU power while the engine is stopped.
  • All configuration dependent values are now possible to use in the flexible Modbus.  
    e.g. power supply measurements (dependent on hardware and number of extension racks) can now be mapped to Modbus.
  • Up to 10 ACM3.1 cards allowed in one controller to be used for measurement (preview feature).

Changes

  • EIC: Volvo Penta EMS2.4: "Engine Override Control Mode" changed to "Speed control".  
  • EIC: Volvo Penta EMS2.4: TSC1 will not be transmitted if VP70 is used for regulation. 
  • Modbus timeout increased from 10 sec to 100 sec on iE 250 and iE 350.  
  • Number of possible Modbus connections changed from 20 to 100 on iE 250 and iE 350
  • Added write permission for "Priorities" when controller is in emulation.

Corrections

  • Fixed issue where changes made in the UI were not registered.
  • Fixed issue where the "IO configuration" menu would show empty slots.
  • Fixed issue where tree-structure menu groups could not be collapsed using touch.
  • Fixed issue where configuring a Modbus value to "true" made the value "255" instead of "1".
  • Fixed issue where measurements from multiple ECUs were not shown in UI for e.g. configuring alarms.
  • Fixed issue where display user could not clear DM2 logs.
  • Fixed issue where iE controller could not start without MIO module. 
  • Fixed issue with missing alarm icons.
  • Fixed issue where user could enter parameter values outside of valid range.  
  • Fixed checksum and counter for VP70.
  • Fixed issue where removing network cable would activate system NOK, IO service error and "temperature too high" alarms. 
  • Fixed issue where CODESYS user management files were not included in the backup/restore.
  • Fixed issue where linked outputs in CODESYS was hidden in IO configuration.
  • Fixed issue where the Genset was not de-loading correctly when it was connected to the Mains.
  • Fixed issue where BUS TIE breaker could not de-load and open a ring connected busbar.